一、 电缆规格要求
外市电低压引入电缆需同时满足载流量、压降及机械强度要求。通信局(站)电源系统技术要求(YD/T 1051-2000)中规定通信电源设备用交流供电时,设备的电源输入端子处测量的电源允许变动范围为:额定电压值的+10%~-15%_
基站市电引入容量主要可按10kW以下、20kW以下两类考虑,对应容量下不同引入距离适用电缆规格如下表所示(不考虑机械强度要求情况下):
380V 10KW(功率因数0.8) 电流约为19A电缆线径电缆载流压降(%) 长度(米)2量(A)(mm)1002004006008004×425铜线3.87.615.222.730.34×10441.53.16.19.212.24×16601.01.93.85.77.64×25810.61.32.53.85.14×351020.50.91.92.83.74×419铝线6.012.023.935.947.94×10342.44.99.814.719.54×16461.53.16.29.312.44×25631.02.04.06.07.94×35790.71.42.94.35.81000200037.975.815.330.69.519.16.312.74.79.359.9119.724.448.915.531.09.919.87.214.5 380V 20KW(功率因数0.8) 电流约为38A电缆线径电缆载流2量(A)(mm)1004×4257.6铜线4×10443.14×16601.94×25811.34×351020.94×501280.74×41912.0铝线4×10344.94×16463.14×25632.04×35791.420015.26.13.82.51.91.323.99.86.24.02.9压降(%) 长度(米)400600800100030.345.560.675.812.218.324.430.67.611.415.319.15.17.610.112.73.75.67.49.32.74.05.46.747.971.895.8119.719.529.339.148.912.418.624.831.07.911.915.919.85.88.711.614.52000151.661.138.225.318.613.4239.497.761.939.729.0 注:1、表格中深色部分表示此处电缆满足要求;
2、交流压降计算依据:人民邮电出版社 《电信工程设计手册》 十七分册 《通
信电源》 第六章 6.3.2 “交流电力线的选择”。
人民邮电出版社 《电信工程设计手册》 十七分册 《通信电源》 第六章 6.3.2 “交流电力线的选择”中给出按机械强度选择导线截面时低压架空裸线的最小线径如下:
铝及铝合金线:16mm2; 钢芯铝线: 16mm2; 铜线:
直径3.2mm2。
二、 市电低压电缆布放技术要求
进入基站的低压电力电缆宜从地下引入机房,其长度不宜小于50m(当变压器高压侧已采用电力电缆时,低压侧电力电缆长度不限)。电缆埋设要求如下:
1、
电缆采用穿难燃PVC套管沿路边直埋,电缆在室外直接埋地敷设的深度:人行道下不应小于0.7m,车行道下不应小于0.8m。
2、
敷设时,应在电缆上面、下面各均匀敷设100mm厚的软土或细沙层,再盖混凝土、石板或砖等保护,保护板应超出电缆两侧各50mm。
3、
电缆穿过下水道等时需穿钢管保护,穿管的内径不应小于电缆外径的1.4倍。
4、 5、
禁止将电缆放在其他管道上面或下面平行敷设。
电缆沿途每隔200米设一个检查井,检查井具体做法见建筑电气安装工程图集JD5-131~133 12#电缆人孔井。
电缆敷设示意图如下:
500100100700电缆土层砖层砂层砂层土层电缆敷设剖面示意图
土层0砖层070砂层00011砂层电缆土层电缆敷设侧面示意图
因篇幅问题不能全部显示,请点此查看更多更全内容